PROBLEM POSSIBLE CAUSE TEST PROCEDURES-
ACTION
Compressor runs, but no Permanent restriction First check for moisture restriction.
refrigeration or insuf- Check for crimped or damaged tubing.
ficient refrigeration Repair or replace restricted component.
Low charge or no charge Check for leak. Add leak charge to
get internal pressure. Repair leak or
replace leaking component.
No capacity or low capacity Check operating wattage and pressure.
compressor. See performance chart for wattage and
high and low side pressures. Do not
judge compressor to have low capacity
until restrictions and low charge have
been ruled out.
Air circulation on high side:
a. Condenser or grille Clean condenser and air passage with
restricted by lint vacuum cleaner.
b. condenser fan motor Disconnect fan motor leads and check
running or running separately. Replace motor if defective.
slowly.
c. Condenser fan motor Put condenser fan motor top cover in
top cover not in place. place.
Compressor kicks out on High ambient and / or ab- On initial pull-down in high ambient,
overload normal usage. the compressor may cut off on overload.
Instruct customer.
Low or high voltage Check voltage with voltmeter. Voltage
at outlet should be 110 to 120 volts AC
at the moment of start. Low voltage
may cause false start s. High voltage
may cause compressor to overheat.
Correct voltage condition.
Run capacitor Check capacitor. Replace if defective.