Component Description Test Procedures
From condenser refrigerant
flows into capillary and then
to evaporator before returning
to compressor through suction
line.
Drier Drier is placed at post Drier must be changed every time the system is opened for
condenser loop outlet and testing or compressor replacement.
passes liquefied refrigerant NOTE: Drier used in R12 sealed system is not inter-
to capillary. changeable with drier used in R134a sealed system.
Desiccant (20) 8x12 4AXH -
7 M>S> Grams. Before opening refrigeration system, recover HFC134a
refrigerant for safe disposal.
1. Score capillary tube close to drier and break.
2. Reform inlet tube to drier allowing enough space for
large tube cutter.
3. Cut circumference of drier 1 1/4" below condenser inlet
tube joint to drier.
4. Remove drier.
5. Apply heat trap paste on post condenser tubes to protect
grommets from high heat.
6. Unbraze remaining part of drier. Remove drier from
system.
7. Discard drier in safe place. Do not leave drier with
customer. If refrigerator is under warranty, old drier must
accompany warranty claim.
Evaporator Inner volume of evaporator Test for leaks in evaporator with electronic leak detector or
allows liquefied refrigerant with soap solution. Compressor oil is circulated with
discharged from capillary refrigerant, check for oil when checking for leaks.
to expand into refrigerant gas. NOTE: Follow all procedures for recovering R134a
refrigerant for safe disposal when opening system.
Expansion cools evaporator For Minute Leaks:
tube and fin temperature to
approximately -20 F
transferring heat from freezer
section to refrigerator. To avoid severe personal injury or death from eruption of high
pressure gases, observe the following.
Passing through suction line Protect against a sudden eruption if high pressures are
to compressor, the refrigerant required for leak checking.
picks up superheat (a relation- Do not use high pressure compressed gasses in
ship between pressure and refrigeration systems without a reliable pressure
temperature that assures regulator and pressure relief valve in the line
complete vaporization of
liquid refrigerant) as result of
capillary in suction line.