15.0 SYSTEM FILL PROCEDURE
15.1 Filling The Reservoir Tank
The CS-1 has been designed to fill the reservoir tank using either of two
methods: gravity fill or pumped fill. NOTE: This is not a self-priming pump.
Manual prime or fill the reservoir for prime.
NOTE: Never leave the unit unattended when filling the system or tank. Running
the pump dry, without liquid, will damage pump seals and possibly damage pump
impeller. Follow the steps below:
15.1.1 Gravity Fill:
1. Turn off and isolate the electrical supply to the unit.
2. Close supply isolation valve.
3. Connect the antifreeze supply container to the supply isolation valve.
A flexible hose may be used, but must not restrict the flow from the
supply container to the valve. An additional isolation valve must be
installed in the line between the supply container and unit’s supply
isolation valve. A slight downward slope from the supply container to
the valve connection is required to prime the pump and maintain
positive head on the pump inlet. Always use a backup wrench when
making piping connections to avoid damage to the unit’s piping.
4. Open the shut off valve on the supply container and supply isolation
valve on the CS-1.
5. Open the pump suction isolation valve and allow liquid to enter the
reservoir tank. If there is enough liquid in the supply container, the
tank may be filled completely using this method. The tank is full when
the liquid level rises to the top of the straight section of the tank.
15.1.2 Pump Assist Fill:
6. If there is not sufficient liquid in the supply container to fill the tank or
the tank fills too slowly, the pump on the CS-1 may be manually
operated to speed up this process. Follow steps 1 to 4 above and 7 to
11 below to fill the storage tank using the pump.
7. Close the pump suction isolation valve and open the tank fill isolation
valve.
8. With the CS-1’s switch in the “OFF” position, turn on power supply to
the unit.
9. Position switches “A” and “B” in the center/off position. Switch the
“OFF-ON” switch to “ON” and the “Man-O-AUTO” switch on the unit
control panel to “Man”. Liquid will begin to fill the storage tank at the
fill connection.
10. Be careful to observe the liquid level to prevent over filling. When the
liquid level reaches the top of the straight section of tank, switch the
unit’s “Man-O-AUTO” switch to off.
11. Close the supply isolation and tank fill isolation valves. Open the
pump suction valve.