An arrow on the pump indicates the correct direction of rotation. If the pump
rotates in the opposite direction, reverse the rotation of the motor. Interchanging
any two incoming 3-phase supply wires reverses rotation of three phase motors.
WARNING: Operating the pump in the wrong direction may damage the pump.
Verify pump rotation is correct before placing the unit in service. Make sure there
is liquid on the suction side of the pump before checking rotation.
Connect system inputs to the proper terminals in the CS-1 control enclosure.
Each system pressure switch and alarm flow switch are connected as shown on
the electrical schematic.
NOTE: All system inputs must be connected before operating the unit. System
valves will not respond unless the system pressure switch and flow alarm switch
are connected correctly.
7.6 Start-Up
The following points must be verified before putting the unit into service. Correct
any discrepancies before operating the unit.
1. The unit is bolted to a firm level surface.
2. Area temperature will always remain between 40 °F and 100 °F (4 and °C).
3. Dielectric unions, if needed, are installed between the pump station piping
and system piping.
4. All piping to and from the pump station is independently supported and does
not place any strain on the unit’s piping.
5. Power supplied to the unit is appropriate (refer to Figure 1 on page 51 d).
5. Pump rotation has been checked and is correct.
6. System inputs are connected according to the electrical schematic.
7. Air can be vented from the system when filling with antifreeze.
8.0 PRESSURE SWITCH
8.1 System Control Switch
The pressure sensor detects the system pressure,
shows the current system pressure on its display and
generates one output signal according to the set output
configuration.
Operating Modes
Run mode: (Normal operating mode)
When the supply voltage has been applied, the unit is in the Run mode. It
monitors and switches the output according to the set parameters. The display
shows the current system pressure. The red LED indicates the switching state of
the output.